[–] 1 pt

That's nonsense. If they are all serviced by the same breaker there is absolutely no reason this would spark more than a code setup. More wires does not mean more voltage.

[–] 0 pt

More current. Voltage should be constant

[–] 1 pt

Voltage causes sparks.

Current is limited at the breaker. More wires does not raise the current limit.

[–] 0 pt

More wires doesn't mean more current load either. All that matters is load. You can have one wire drawing 20A and it's out of spec on a 15A circuit, or you could have 400 wires each feeding a 3mA load and everything is fine.