House battery project is almost done but the required terminating resistor is AWOL. I only have a couple 100s and lots of 470s. I could get close by paralleling 2 100s and put another 100 in series --> 150 Ohms. Or parallel four 470s --> 118 Ohms.

I don't know about the tolerances for Modbus termination. Anyone know if a single 100 Ohm resistor has a chance of working?

Edit: Cable length is about 29 ft (~9 meters) Cat6

House battery project is almost done but the required terminating resistor is AWOL. I only have a couple 100s and lots of 470s. I could get close by paralleling 2 100s and put another 100 in series --> 150 Ohms. Or parallel four 470s --> 118 Ohms. I don't know about the tolerances for Modbus termination. Anyone know if a single 100 Ohm resistor has a chance of working? Edit: Cable length is about 29 ft (~9 meters) Cat6

(post is archived)

[–] 0 pt

Thanks a lot. Got the installation done today and everything works flawlessly. All the components talk to each other.

Still it's good to know that a TP cable with a lower gauge might help.